CleaverBrooks Suggested Water Quality Level

ASME WATER QUALITY

Cleaver-Brooks requires industrial watertube boiler water quality to be maintained in strict accordance with ASME guidelines outlined below:

ASME Document No. CRTD (Vol. 34)

“Consensus On Operating Practices For the Control of Feedwater & Boiler Water Chemistry in Modern Industrial Boilers”

Table 1:

Suggested Water Chemistry Limits, Industrial Watertube, High Duty, Primary Fuel Fired, Drum Type

* as CaCO3

NS = not specified

ND = not detectable

VAM = Use only volatile alkaline materials upstream of attemperation water source. (10)

4.1.1- New Installations
A new hydronic system may contain various kinds of debris from the construction process, including weld slag, metal shavings, etc. The piping system should be thoroughly flushed with the boiler isolated from the system to ensure particulates do not enter the boiler.

During this and any subsequent cleaning or flushing of the system, take care to ensure that no debris enters the boiler during the cleaning process. Consult with the installation contractor and/or water treatment provider for filtration recommendations. A pre-start “boil out” of the vessel is not required; the interior boiler surfaces are cleaned following production of the pressure vessel.