While it is important to consider equipment concerns at all times, maintaining system water condition is equally important for keeping the cooling processes at full capacity and continuing effective operation of the cooling tower.
Consider the cooling tower, along with the other mechanical components, as the cooling system hardware, while the water flowing through the cooling tower is the system software.
Water condition is not often thought of as a potential variable over time. The cooling water essentially is invisible to the operator, but when left unattended, water supports biological growth, and corrodes or scales equipment. Proper ongoing treatment is important to process operation and efficiency.
Cooling loops remove waste heat from the process and function by allowing water to evaporate to the atmosphere. The evaporated water must be replaced continuously by fresh make-up water.
Without a bleed stream, commonly known as blowdown, the dissolved solids in the original system’s water volume, plus dissolved solids added by the make-up water, will accumulate in the system until precipitation begins. Eventually an unbled system will fill with solid scale material.
To balance the incoming water solids, a small portion of the circulating water stream with its elevated solids level is removed to drain. An equilibrium is then established between the added water replacing evaporation and high solids water losses, drift and blowdown.
The term cycles of concentration is defined as the resulting ratio of concentrated solids in the circulating water compared to that in the fresh makeup. Calculation of cycles is performed using the following equation. Alternatively, the blowdown required to establish a given equilibrium-cycles level can be derived from this equation:
It is the open nature of these systems that determines the unique water problems that they exhibit. Cooling towers concentrate solids and the air contact in these open systems allows the buildup of contaminants, organics, bacteria and their food sources in the circulating cooling water.
These unique evaporative water system problems — concentration and air washing — must be dealt with or process disasters will follow. Water is both the static and dynamic basis for controlling such problems.
Poor water maintenance will create certain and predictable problems in open cooling loops. These problems are detailed below:

Scale formation is the creation of a precipitated solid. By coating heat exchange surfaces, this solid material interferes with efficiency of the system’s heat exchange surface and also blocks water flow at the cooling tower’s basin or fill. Cooling-loop precipitates generally are calcium carbonate crystals. In a few cases, these are calcium sulfate or silica solids. Scaling occurs because specific dissolved solids, in the case of calcium carbonate scale, namely calcium and bicarbonate alkalinity, have exceeded their solubility limits and are forming solids. Calcium carbonate crystals commonly precipitate on critical surfaces, like the heat exchanger tube interior walls. The scale thickens the barrier to heat transfer, thus reducing the efficiency of the cooling system.

Corrosion is the process of metal dissolution, usually by oxidation, resulting in substantial material breakdown and premature degradation of system equipment. The oxidation process, in a very simplified form, is the movement of electrons from metal system components into the water medium provided in wet systems and subsequently to a corrosion product of substantially different form than the original base material. This process degrades the metal, reduces its strength, thickness, and in some extreme cases, creates pits and then holes in the material. At some point in the corrosion process, the metal can no longer do its job as a system component. Corrosion, in general, and pitting corrosion, in particular, must be guarded against in order to ensure the long term integrity of the cooling system.

Water left unattended for any significant length of time will grow bacteria, fungi, algae and even protozoa. This diversity of growth, allowing organisms to flourish in a protected environment, results in well established and difficult-to-remove biofilm. This growth process and its attachment to system surfaces is called biological fouling. This growth is considered by many to be the root of most cooling-loop water treatment problems. Those problems include heat transfer efficiency reduction, cooling tower fill fouling, water flow blockages, microbiologically induced corrosion and human health concerns. All of these effects are dramatic and serious. Biological control must, therefore, be a primary part of good water system control.
There are a number of strategies for combating each of the problems described above. One must evaluate the system components, the available water and water management techniques available for a given site to determine the best solution for a specific case. Below are discussions of the control techniques for each problem area.
In order to continuously and effectively operate a cooling system and establish sound biological control, first eliminate nutrient sources that may add material to the system, such as oil leaks, process fluid leaks and the like.

Second, limit the air-wash effect of the cooling tower, which naturally adds nutrients and bacteria to the system, by filtration for removal of suspended solids and the bacteria that reside on them. Effective filtration can be done either with centrifugal separators or sand filters. A front-end strainer also is essential.
Finally, it is critical to provide a consistent and effective biocide addition to the system. In most cases this is a chlorine or bromine. Because of regulatory pressures, one might consider other cooling water biocides like ozone or hydrogen peroxide. These compounds are very effective biocides when properly applied and ozone can be used as a stand-alone treatment in most HVAC cooling systems. In a conventional chemical treatment system, a service provider or self-administered water maintenance program consists of adding an oxidizing biocide and a combination scale and corrosion inhibitor to the water system. One should monitor chemical treatment to determine the effectiveness of the program. This will prevent major operating problems in the system. In a number of cases, additional, specific additives may be necessary to avoid unique problems presented by operating water chemistries and specific site issues.